March 18, 2025
193 - Fire Fundamentals pt. 15 - Extinguishing systems with Bogdan Racięga

The player is loading ...

Welcome to another Fire Fundamentals. This time the episode is focused on various extinguishing technologies. Invited guest - Bogdan Racięga, Director at Baltic Fire Laboratory and expert in fire protection systems breaks down the fundamental differences between suppression and extinction technologies and how they work in real-world applications.
- Clear distinction between suppression systems (control fires while meeting temperature criteria) and extinction systems (must completely extinguish fires)
- Types of fire protection systems including water-based (sprinkler, water mist), foam, aerosol, and gas systems (no fire-balls :))
- Technical parameters affecting performance: K-value, nominal working pressure, RTI, discharge areas
- Areas of application, eg. why water mist systems can often be preferred for high-rise buildings due to smaller piping and reduced weight
- How temperature ratings and RTI affect sprinkler activation timing and performance
- Challenges with concealed sprinklers including maintenance issues and delayed activation
- Testing procedures for water distribution patterns and certification processes
- Differences between high-pressure and low-pressure systems in various applications
- nuances related to the role of an accredited laboratory (ISO 17025) and a certification body (ISO 17065)
----
The Fire Science Show is produced by the Fire Science Media in collaboration with OFR Consultants. Thank you to the podcast sponsor for their continuous support towards our mission.
Transcript
WEBVTT
00:00:00.381 --> 00:00:02.144
Hello and welcome to the Fire Science Show.
00:00:02.144 --> 00:00:04.748
Last week we had fire fundamentals and guess what?
00:00:04.748 --> 00:00:07.514
This week we're talking fire fundamentals once again.
00:00:07.514 --> 00:00:16.195
Last week we've talked about jet fan systems and ventilation and today I'm venturing in the world as far from that as possible.
00:00:16.195 --> 00:00:17.960
Well, maybe not that far.
00:00:17.960 --> 00:00:23.405
Actually, I'm switching the theme from air to water or to other extinguishing agents.
00:00:23.405 --> 00:00:31.414
From air to water or to other extinguishing agents and in this episode of Fire Science Show we will cover the basics of suppression and extinguishing technologies out there.
00:00:31.414 --> 00:00:41.340
So we will talk about water-based systems, we'll talk a little bit about other types of extinguishing systems that you can find out there and obviously I'm not an expert.
00:00:41.340 --> 00:00:51.490
I feel comfortable talking about jet fans, pressurization or any sort of smoke control for you, but I'm definitely not an expert in any suppression or extinguishing applications.
00:00:51.490 --> 00:00:52.593
I even mix the terms.
00:00:52.593 --> 00:00:58.588
So I've invited an expert that I know and I respect highly my good colleague, Bogdan Racięga.
00:00:58.588 --> 00:01:13.250
Bogdan is a director at the Baltic Fire Laboratory, chairman of the scientific council at the International Water Misassociation and a member of numerous NFPA panels, like 750, 502 or 409.
00:01:13.250 --> 00:01:19.087
And the Baltic Fire Laboratory it's the laboratory in Poland that specializes in testing suppression and extinguishing applications, and I've been there multiple times.
00:01:19.087 --> 00:01:21.040
I've seen the experiments out there.
00:01:21.040 --> 00:01:27.164
It's very impressive and definitely, definitely they've gained a huge body of knowledge on how those systems work.
00:01:27.545 --> 00:01:37.212
In this podcast episode we will go a little bit deeper into how they work, but really the point is to recap the fundamentals, to test the point of fire fundamentals.
00:01:37.212 --> 00:01:41.730
Let's recap the fundamentals and learn the basic differences between the systems.
00:01:41.730 --> 00:01:45.129
What are the parameters that characterize the systems?
00:01:45.129 --> 00:01:49.811
How do those parameters turn into actions on buildings?
00:01:49.811 --> 00:01:51.665
Why would you care about pressure?
00:01:51.665 --> 00:01:53.406
Why would you care about discharge?
00:01:53.406 --> 00:01:56.310
How does it change the outcomes on the fire?
00:01:56.310 --> 00:01:59.969
How do you choose the correct application for the problem at your hand?
00:01:59.969 --> 00:02:05.448
These are the things that I wanted Bongdan to cover and I think he quite well delivered that.
00:02:05.448 --> 00:02:14.461
So even if you're an expert in suppression or extinguishing, this episode should have some good nuggets of knowledge even for you.
00:02:14.461 --> 00:02:36.503
And if you're coming to the world of fire from structural engineering, mechanical engineering, chemical engineering you're not a fire safety engineer but yet you have to work with the fire problem and you have not really been exposed to those extinguishing systems, this is an episode for you that will give you a kickstart into the profession and cover the basics for you, so I'm really proud to introduce you to this episode.
00:02:36.503 --> 00:02:38.429
I hope you will have a good time listening to it.
00:02:38.429 --> 00:02:40.881
Let's spin the intro and jump into the episode.
00:02:40.881 --> 00:02:47.024
Welcome to the fire science.
00:02:47.024 --> 00:02:50.485
My name is Wojciech Wigrzyński and I will be your host.
00:03:06.014 --> 00:03:13.538
This podcast is brought to you in collaboration with Ofar Consultants, a multi-award winning independent consultancy dedicated to addressing fire safety challenges.
00:03:13.538 --> 00:03:25.207
Established in the UK in 2016 as a startup business of two highly experienced fire engineering consultants, the business has grown phenomenally to eight offices across the country, from Edinburgh to Bath.
00:03:25.207 --> 00:03:34.719
Colleagues are on a mission to continually explore the challenges that FHIR creates for clients and society, applying the best research experience and diligence for effective, tailored solution.
00:03:34.719 --> 00:03:38.691
In 2025, there will be new opportunities to work with OFR.
00:03:38.691 --> 00:03:46.603
Ofr will grow its team once more and is keen to hear from industry professionals who would like to collaborate on fire safety features this year.
00:03:46.603 --> 00:03:49.628
Get in touch at ofrconsultantscom.
00:03:50.211 --> 00:03:50.752
Hello everybody.
00:03:50.752 --> 00:03:54.794
I am here today with my good friend, bogdan racenga from baltic fire laboratory.
00:03:54.794 --> 00:03:56.622
Hello, bogdan, good to have you in the podcast again.
00:03:56.622 --> 00:03:57.667
Hello, boy checking.
00:03:57.667 --> 00:03:59.092
Thank you for invitation again.
00:03:59.092 --> 00:03:59.996
Yeah, thanks, man.
00:03:59.996 --> 00:04:04.688
I so many times in my life when I said I'm having extinction.
00:04:04.688 --> 00:04:10.651
You've corrected me I'm having suppression, so I thought that perhaps let's clear this once and for all on air.
00:04:10.651 --> 00:04:20.095
But really there's so many nuances around sprinklers and extinguishing and suppressions that I believe a lot of people will benefit from learning.
00:04:20.095 --> 00:04:23.009
But let's start with that one like extinction versus suppression.
00:04:23.009 --> 00:04:25.427
Why the hell are you correcting me all the time, bogdan?
00:04:25.988 --> 00:04:31.411
Yeah, exactly, because, especially in our Polish language, there's not exactly a word about the suppression system.
00:04:31.411 --> 00:04:36.391
The people are saying extinguishing system, extinction system.
00:04:36.391 --> 00:04:46.583
So in our laboratory, when we are testing this active fire protection system, we have clear differences between the extinguishing system and the separation system.
00:04:46.583 --> 00:04:54.846
So, in very short words, the extinguishing system is a system which must extinguish the fire in the specific time.
00:04:54.846 --> 00:05:08.747
If this time is like 15 minutes, 30 minutes, you need to achieve the full extinguishing of the fire which is in the specific place, the most probably in our enclosures.
00:05:08.747 --> 00:05:10.793
And this is the extinguishing system.
00:05:10.793 --> 00:05:16.987
And the suppression system has a specific time to achieve specific suppression criteria.
00:05:16.987 --> 00:05:23.629
This suppression criteria means ceiling temperature and the damage of the object which is in the fire Actually makes sense.
00:05:23.651 --> 00:05:30.430
So extinction would be like getting rid of the fire completely, and suppression would be minimizing the outcomes of the fire, correct?
00:05:30.800 --> 00:05:32.827
And then you have the specific application.
00:05:32.827 --> 00:05:34.848
I give you example for that.
00:05:34.848 --> 00:05:39.351
So the extinguishing system we are using mainly in the machinery space turbine enclosures.
00:05:39.351 --> 00:05:43.271
So then the system is dealing with the fire itself.
00:05:43.271 --> 00:05:50.113
You do not counting on any fire brigade or any crew in this factory, on this marine vessel, for example.
00:05:50.113 --> 00:05:58.000
So the system inside the laboratory is tested in such a way that it's able to kill this fire within 15 minutes.
00:05:58.000 --> 00:06:02.992
If you are, for example, telling about the IMO 1165 test methods for the total flooding.
00:06:03.439 --> 00:06:09.745
Then the suppression system, like we have the systems with the sprinkler and the water mist in the hotels, for example.
00:06:09.745 --> 00:06:14.692
So this system has some limits on the ceiling in terms of the temperature.
00:06:14.692 --> 00:06:19.672
We can divide the fire tests to the reference tests with the sprinkler and the water mist.
00:06:19.672 --> 00:06:22.274
Then the sprinkler system we are running first.
00:06:22.274 --> 00:06:40.648
This is a test that is making a base for our test criteria for the water mist system and the water mist system in terms of the temperature on the ceiling shall be on the same level or better, and the damages on the object, like the office desk and the sofa, should be in better results.
00:06:40.648 --> 00:06:43.247
It means the damage with the water mist must be less.
00:06:43.427 --> 00:06:44.190
Like the sprinkler.
00:06:44.190 --> 00:06:45.930
There are as well some test protocols that you mist must be less like the sprinkler.
00:06:45.930 --> 00:06:50.661
There are as well there's some test protocol that you do not need to run the sprinkler system when you are testing the water mist system.
00:06:50.661 --> 00:07:01.351
So there, you have clearly defined the temperature on the ceiling that you cannot cross and the damage on the object which is in the fire, and this is suppression.
00:07:01.351 --> 00:07:06.250
It means after 30 minutes, still you have the fire, but you are going to terminate the test.
00:07:07.540 --> 00:07:11.800
I'm going to be called a lobbyist, but I always wondered why sprinkler systems do not require a reference.
00:07:11.800 --> 00:07:13.646
What are these tests to compare them to?
00:07:13.646 --> 00:07:17.704
And perhaps that's not good Damage.
00:07:17.704 --> 00:07:22.228
We'll go back into the systems because that's on the long list of questions they have for you.
00:07:22.228 --> 00:07:28.447
But you mentioned damage to the items around the sprinklers or whatever device is operating.
00:07:28.447 --> 00:07:32.069
So what do you actually mean by saying limiting damage?
00:07:32.069 --> 00:07:33.326
How do you assess the damage?
00:07:33.326 --> 00:07:35.225
How does it look in the experiment?
00:07:35.225 --> 00:07:35.728
Yeah, okay.
00:07:35.860 --> 00:07:40.295
So let's fix to the object which is in the fire, which is the sofa.
00:07:40.295 --> 00:07:55.987
Okay, it consists of the two sofas, which is like the eight materats, and we have the sidewall test, for example, where we have the sofa in the fire and after 30 minutes the sofa cannot be burned more than 40% of the total volume.
00:07:55.987 --> 00:08:02.706
So after the fire tests, we have the special technique as a laboratory to measure this 40%.
00:08:02.706 --> 00:08:08.007
If we are above, it means failure and if we are below, it means pass.
00:08:08.579 --> 00:08:12.879
And I guess every different protocol that you test for would have its own criteria.
00:08:12.879 --> 00:08:19.992
I remember when I was visiting your laboratory, you were having this vehicle mock-up and you had some wood planks next to the vehicle.
00:08:19.992 --> 00:08:23.048
Yes, so these were the damage targets for assessments Correct.
00:08:23.220 --> 00:08:38.707
So in this test which you've seen, it was IMO 1430 with the passenger vehicle which representing the fire, or the car on the 2.5 meter ceiling, which is quite low, as we discussed, and inside there was the 12 pallets.
00:08:38.707 --> 00:08:46.227
In this test the damage itself on the pallets is not counted, it's counted the temperature on the ceiling.
00:08:46.227 --> 00:08:54.783
And then important in this test is if the targets, which was on the left and on the right, the play woods, are ignited or not.
00:08:54.783 --> 00:09:09.190
And then this information, if the play woods are ignited or not, for the lab is a challenge as well sometimes to found, because the wood, despite is wet by the water, may burn within 400 Celsius even.
00:09:10.303 --> 00:09:20.171
I knew it's a good idea to bring you to the podcast, and the stuff that we're discussing right now is so important to engineers to understand what is behind the numbers.
00:09:20.171 --> 00:09:50.778
Like, people very rarely know what does fire resistance of 30 minutes really mean unless they've seen a fire test in a fire laboratory or have a very specific methodology to assess that this particular device is fit for actually quite a representative scenario of hazard.
00:09:50.778 --> 00:09:56.320
Do scenarios like that like they really exist for almost any accommodation?
00:09:56.320 --> 00:10:07.062
Like every time you see a different sprinkler type, it means there's a specific test describing the fire for a specific location and it has to go to protocol, or it's like I don't know.
00:10:07.062 --> 00:10:15.192
Uh, they use tests for car parks as I say, okay, this is gonna be fit for, I don't know, changing rooms and and bicycle storage and and metro stations.
00:10:15.192 --> 00:10:16.195
How does it work?
00:10:16.275 --> 00:10:19.767
okay, so I I will go in such way with the sprinklers.
00:10:19.767 --> 00:10:30.634
You are mainly have this value of the millimeters of the water in the square meter which you have, the value for the specific hazard and you can follow with this value, okay, okay.
00:10:30.634 --> 00:10:37.150
Okay, I explain this the best, I think, with reference to the performance-based system.
00:10:37.150 --> 00:10:39.154
It means the water mists.
00:10:39.154 --> 00:10:41.326
Why it will be better?
00:10:41.779 --> 00:11:08.605
Because when you have the fire in the office and the fire in the car park, those are the two different fires and, of course, the car park is the most challenging one comparing to the office, because of the quantity of the fuel load which you have in the office or in the hotel, for example, nozzle or sprinkler head which is dedicated for the car park or dedicated for the office.
00:11:08.625 --> 00:11:19.759
The quantity of the water for the car park is much higher because it's related to the density, yeah, so oh2, like for the sprinklers, 80 millimeters per square meter in the europe which is quite common.
00:11:19.759 --> 00:11:23.649
It's a kind of value for the water-based system.
00:11:23.649 --> 00:11:33.785
Sprinkler with the water mist is different because, again, you have the reference tests with the sprinkler system and after you are creating your pass-fail criteria based on the sprinkler test.
00:11:33.785 --> 00:11:39.003
So where the water mist system if it's high pressure or if it's low pressure.
00:11:39.003 --> 00:11:46.315
In the car parks the density comparing to the OH1 commodity, like in the office, is much, much higher.
00:11:46.315 --> 00:11:55.972
And it's important as well in those tests that in the car parks, for example, the area of the operation, call it the most demanding area, it's 144 square meters.
00:11:56.340 --> 00:12:00.392
And in the OH1 spaces it's like 72 square meters.
00:12:00.392 --> 00:12:18.687
It means in our tests we are testing the system and there are specific heads sprinkler heads or water mist heads which can operate during the test and if some of the heads will operate outside of the specific ring, the test is failed.
00:12:19.068 --> 00:12:39.384
It means this justifies you that the system was able to stop the fire spread and the temperature are maintaining very well on the ceiling so you have also like reference things, like the areas like the flow rates, uh discharge values that allow you to generalize some, some concept, and still, I would assume, those uh correlation that you need.
00:12:39.384 --> 00:12:43.863
This particular oh2 setting for carport comes from experience and testing.
00:12:43.863 --> 00:12:50.227
Yes, um, we brought up many names for those different systems, so perhaps let's clean this up a little bit.
00:12:50.227 --> 00:12:53.890
I don't think I've had such discussion in Fire Science Show yet.
00:12:53.890 --> 00:12:57.107
So we were talking about Sprint, we were talking about Watermist.
00:12:57.107 --> 00:12:58.311
Let's clean it up.
00:12:58.311 --> 00:13:07.729
What types of systems extinction or suppression systems, what kind of systems are there on the market that that the fire engineers could meet in their jobs?
00:13:08.289 --> 00:13:12.761
okay, so generic, about the system which you can find everywhere.
00:13:12.761 --> 00:13:13.443
Of course.
00:13:13.443 --> 00:13:14.908
We have the water-based system.
00:13:14.908 --> 00:13:16.972
It means the sprinkler, the water mist.
00:13:16.972 --> 00:13:32.870
Then we have the foam system, which are helping us to fight with the pool fires, mainly areosol system, the system which are testing a lot now because of some changes on the market, gas system, like the clean agent inert guard system.
00:13:32.870 --> 00:13:41.279
So those are mainly those which I mentioned here, and each of them has a specific purpose and application as well.
00:13:41.279 --> 00:13:51.506
You cannot use each of the system to all the application, so the key point is to understand which system shall be addressed to your application.
00:13:51.506 --> 00:14:01.644
This is the most critical to understand and know the strong sides and the weak sides as well of those extinguishing or the suppression systems.
00:14:02.140 --> 00:14:03.988
You have not mentioned extinguishing balls.
00:14:04.600 --> 00:14:24.419
No, no, this is something that I'm struggling a lot because, from last to most, these extinguishing balls are called aerosol generators, because the aerosols are quite successful on the market and there could be serious competitions for the protection of some applications.
00:14:24.419 --> 00:14:29.072
So those guys are starting to tell that this is aerosol generator.
00:14:29.072 --> 00:14:30.225
It's completely not.
00:14:30.225 --> 00:14:34.989
Maybe it's bomb, but it's not the generator of aerosol definitely.
00:14:35.690 --> 00:14:36.392
No, definitely.
00:14:36.392 --> 00:14:41.451
Okay, good, so we would have water-based systems and we would have gas-based systems.
00:14:41.451 --> 00:14:44.865
We would have aerosol-based systems, A lot of stuff to choose and the basic differences between, let's say, the gas-based systems.
00:14:44.865 --> 00:14:48.755
We would have aerosol-based systems, a lot of stuff to choose and the basic differences between, let's say, the water-based systems.
00:14:48.755 --> 00:14:53.711
So I mean, it's obvious that water mist gives you mist or fog.
00:14:53.711 --> 00:14:57.590
The sprinklers give you this nice big spray of water.
00:14:57.590 --> 00:15:01.510
I think the fire engineers would intuitively understand that very well.
00:15:01.510 --> 00:15:09.535
And from a technical perspective, like on the technical properties when you design those systems, yes, what are the major differences?
00:15:09.976 --> 00:15:10.277
okay.
00:15:10.277 --> 00:15:18.933
So each sprinkler the water means we must divide to the open nozzles or bulb nozzles, correct automatic sprinkler.
00:15:18.933 --> 00:15:27.434
So this open nozzles, called the dilution theler world, are the systems which are connected with the dry pipe system.
00:15:27.434 --> 00:15:46.625
It means you have the electronic valve which is triggered by the fire detection system and then you are releasing the water for the specific protection those systems are common in protection of some industry parts like the conveyors, tunnels, tank protection by the cooling as a deluge system.
00:15:47.620 --> 00:15:53.467
So you have like 20 sprinklers on a pipe and they all go off together when the fire alarm tells them to do so.
00:15:53.467 --> 00:15:55.947
Exactly, I think that's what we do in tunnels, right.
00:15:56.148 --> 00:16:05.293
Yes, exactly, and you have the specific area and the quantity of these heads, because this is again connected with the area of the operation and the sizing of the pump.
00:16:05.293 --> 00:16:16.773
So you cannot run more than calculated sprinklers in specific zones because then you do not reach the pressure which is the nominal working pressure on the head.
00:16:16.773 --> 00:16:26.835
So when in the laboratory you have the nozzle on the sprinkler tested with the two bars, you must deliver the two bars during the fire, in the tunnel, for example.
00:16:26.835 --> 00:16:36.169
This is the critical value that the flow rate, together with the pressure and the curve value of the nozzle must be respected in case of the fire.
00:16:36.169 --> 00:16:45.265
That's why there are some safety factors on the design side added, despite the tests done in the laboratory and after the open nozzles.
00:16:45.265 --> 00:16:52.139
Of course we have the bulk system, very complex sprinklers with the bulbs inside glass bulb Depends on the sensitivity.
00:16:52.139 --> 00:16:56.572
You have this RTA number which is defining how fast are those bulbs.
00:16:56.572 --> 00:17:04.730
This can be the standard fast response or even super response for some very specific applications.
00:17:04.730 --> 00:17:07.067
And those sprinklers you can find in the hotels.
00:17:07.067 --> 00:17:11.130
There is digital buildings, storage areas, garages, commercial buildings, everywhere.
00:17:11.130 --> 00:17:14.288
Almost those are the most fun with sprinkler system.
00:17:14.288 --> 00:17:14.650
Come on.
00:17:14.650 --> 00:17:17.046
So this was about the sprinkler.
00:17:17.400 --> 00:17:27.030
Now the area where is the most challenging for me and interesting as well, because we are running 65% of the old tests with the Waterme system.
00:17:27.030 --> 00:17:29.444
So again the open nozzles.
00:17:29.444 --> 00:17:34.685
It means triggered by the fire detection system and they're connected with the dry pipe.
00:17:34.685 --> 00:17:46.351
All section is going in the same time and the quantity of the nozzles multiply by the flow rate, giving you this information what the pump's size should be.
00:17:46.351 --> 00:17:57.792
Typical application machinery space generators, tunnels, aircraft, hangars, turbine enclosures, specific hazards, like the other machinery spaces.
00:17:57.792 --> 00:18:00.207
So those are the open nozzles.
00:18:00.207 --> 00:18:10.166
Then the bulk nozzles, the water miss nozzles has mostly faster RTI because the nozzles are quite smaller.
00:18:10.166 --> 00:18:13.088
You have the low pressure system, you have the high pressure systems.
00:18:14.401 --> 00:18:21.134
So we've seen those water miss systems, especially on the marine from the 30 years because it was there.
00:18:21.134 --> 00:18:28.929
Now in the land are widely used because in the European 4972 just entered, like five years ago.
00:18:28.929 --> 00:18:34.153
So now the engineer is able to put in the technical building specification the standard.
00:18:34.153 --> 00:18:36.665
Previously it was challenging because there was no standard.
00:18:36.665 --> 00:18:45.787
So we've seen those systems in the hotels, residential buildings Again about the marine in all these public spaces, restaurants, cabins.
00:18:45.787 --> 00:18:49.164
So very similar application to the sprinkler.
00:18:49.164 --> 00:18:54.555
But there are some areas where the sprinkler are better and where the water miss are better.
00:18:54.555 --> 00:19:13.076
Example Warsaw is a great example because it's buildings have a high-pressure water system because of the hate to reach to the last floor and the water head automatically as well.
00:19:13.801 --> 00:19:15.040
Why would that be Okay?
00:19:15.040 --> 00:19:21.513
Because with the sprinkler system when you're protecting the high-size buildings you must be challenging this water head.
00:19:21.513 --> 00:19:33.500
It means your pump must deliver to the dry riser the most probably or there are the wet risers as well the specific pressure For the certifigular pumps for the certain value.
00:19:33.500 --> 00:19:36.105
It's impossible to reach more.
00:19:36.105 --> 00:19:41.961
Then you need to build inside of your floors the water tanks for the sprinkler system.
00:19:41.961 --> 00:19:52.269
With the water system you have one tank in the basement and one pump unit in the basement and you can protect all the building.
00:19:52.269 --> 00:20:08.847
And I know in the Warsaw the building which is the highest rise, which has 22,000 nozzles of the water nests, which is quite massive, and those are the two pump units in the basement and this is quite a nice project.
00:20:08.847 --> 00:20:16.171
This is a few in Warsaw quite prestigious projects and luckily in Warsaw is the highest building in the European Union as well.
00:20:17.101 --> 00:20:18.666
Half a meter taller than short.
00:20:18.666 --> 00:20:29.839
Yes, to your face, our British colleagues, we have a half a meter taller building, apparently not by accident Because of the antenna, because of the antenna only.
00:20:29.839 --> 00:20:32.609
No, no, it's a structural part of the building.
00:20:32.609 --> 00:20:33.192
It's important.
00:20:33.192 --> 00:20:34.998
Okay, let's not go there.
00:20:34.998 --> 00:20:45.028
And also, for me, a difference that was obvious when I was talking with people like the difference between Splinkus and Watermist, for example, was with the piping.
00:20:45.028 --> 00:20:54.632
So, so every time it was brought up on the project, people oh, I would prefer, you know, a water mist because it has this, those nice little pipes and and not, uh, big pipes like, like sprinkles have.
00:20:54.632 --> 00:20:58.147
So perhaps let's talk, let's talk about that exactly.
00:20:58.147 --> 00:20:59.371
So it's those differences.
00:20:59.411 --> 00:21:23.868
Yeah, it's very good point for attack and, of course, with the water miss system, especially with the high pressure, you are able to drop the size of the pipes which delivering the water to the 38, 42 millimeters, maybe 60 millimeters as a main pipe which is just going from the basement to the 52 floor, but with the sprinkler system we are talking about 150 to 100 millimeters.
00:21:23.868 --> 00:21:31.167
And then we are going to the weight of all this system, which is a crazy with the sprinkler.
00:21:31.167 --> 00:21:42.086
So, as I told, the sprinkler is good for some application and the water mist is perfect for some and for the high-rise buildings the water is really perfect because we are saving a lot of material.
00:21:42.086 --> 00:21:47.987
Then, with the materials, you have the penetration between the bulkhead, between the walls, between the floors.
00:21:47.987 --> 00:21:58.517
So all these penetrations are extremely expensive as well and these penetration sizes are as well higher in terms of the price if you have the bigger penetration as well.
00:21:58.517 --> 00:22:01.650
So this is something that is really good.
00:22:01.859 --> 00:22:08.844
Okay, we will get argument, but the water mist system has the stainless steel pipes, which is expensive Anyhow.
00:22:08.844 --> 00:22:17.028
If you're comparing the weight of the system and the price of the stainless steel, comparing to the weight of the standard seal for the sprinkler installation.
00:22:17.028 --> 00:22:29.029
The water mist win anyhow with the price Because if we are talking about the 22,000 of the high-pressure water mist nozzles, it's a huge weight of the system.
00:22:29.029 --> 00:22:33.846
So anyhow, there will be a beneficial for the water mist systems.
00:22:35.484 --> 00:22:41.160
I know there's like this market battle between the water mist industry and the sprinkler industry.
00:22:41.160 --> 00:22:47.346
You see it every day on on real world projects, where people try to replace one solution with another, both.
00:22:47.346 --> 00:22:48.209
But I like that.
00:22:48.209 --> 00:22:52.667
There are technical merits at which you can discuss and technical merits at which you want.
00:22:52.667 --> 00:22:55.717
That is a challenging world, but I like that.
00:22:55.717 --> 00:23:04.351
There are, you know, technical properties of the systems that you are able to to compare the solutions and actually find one that fits best for your needs.
00:23:04.351 --> 00:23:04.550
Right?
00:23:04.550 --> 00:23:10.885
I was noting down, you know, when you were dropping, a technical term we have not explained yet and I have quite a list right now.
00:23:10.885 --> 00:23:18.594
There's nominal working pressures, k-values, rti, discharge areas, the most challenging location, and so on.
00:23:18.594 --> 00:23:21.128
So perhaps let's try and cover those.
00:23:21.128 --> 00:23:27.074
It's supposed to be an introductory episode, so let's try to go through the basics.
00:23:27.074 --> 00:23:30.630
So first let's talk about the nominal working pressures.
00:23:30.630 --> 00:23:37.670
You said that you would design for a nominal working pressure, but what does it mean and how much you can debate from that?
00:23:38.220 --> 00:23:38.540
Okay.
00:23:38.540 --> 00:23:59.271
So when we are testing those systems in the laboratory, there is the specific test for the sprinkler or the water mist where we have to maintain the nominal working pressure in the test, which is the minimum nominal working pressure that the nozzle in real life, in the real installation, must achieve.
00:23:59.271 --> 00:24:02.131
The most probably depends on the calculation.
00:24:02.131 --> 00:24:11.587
This nozzle is the most furthest nozzle in the section hydraulic section and some of the nozzles which are closer to the pump has higher pressure automatically.
00:24:11.587 --> 00:24:17.664
And about the deviation for the example, for the low pressure mists we have the 5% deviation.
00:24:17.664 --> 00:24:29.374
So during the test where we have the 5 bar or the 8 bar for the low pressure mist system, we cannot cross below minus 5% and the plus 5% during the entire test.
00:24:30.119 --> 00:24:35.353
The same high pressure systems what we've seen in our laboratory conditions.
00:24:35.353 --> 00:24:42.371
Sometimes it's better to maintain the pressure in the high pressure system because the high pressure system has piston pumps.
00:24:42.371 --> 00:24:45.369
It means the characteristics of these pumps are very linear.
00:24:45.369 --> 00:24:51.165
So you are able, depending on the RPMs on your pump, to set precisely the pressure.
00:24:51.165 --> 00:24:59.029
With the low pressure system and with the sprinkler system you have the certificular pumps which have the specific curve and characteristics of the pump.
00:24:59.029 --> 00:25:07.692
So we need to deal a little with this characteristic and some unload valve, pressure reduction valve, just to set correctly the pressure.
00:25:07.692 --> 00:25:24.232
So those are the main system and the nominal working pressure always must be the nominal pressure in the installation and during the commissioning of the system, when the system is to the authority, this must be checked on this most remote nozzle in the hydraulic section.
00:25:24.574 --> 00:25:28.690
if you achieve those, I assume that you cannot have it lower, but what happens if it's higher?
00:25:28.690 --> 00:25:30.788
Because if you're closer to the pump it must be higher.
00:25:31.279 --> 00:25:31.480
Okay.
00:25:31.480 --> 00:25:36.972
So if you are higher with the sprinkler system, you are delivering much more water.
00:25:36.972 --> 00:25:48.728
But the sprinkler system of course does not cross like the 10 bar or the 16 or the 20 bar, so we can assume that it's better because you have more water.
00:25:48.728 --> 00:26:07.181
Okay, in the low pressure system you have this specific five percent because the nozzle of the low pressure mist system are designed in such way, very precise way, that the spray pattern above some limits may change, which affect the test criteria.
00:26:07.181 --> 00:26:11.590
If you are above, okay, you are delivering as well much more water.
00:26:11.590 --> 00:26:16.307
It means for the test criteria can be better with the high pressure systems.
00:26:17.269 --> 00:26:26.943
We found a funny discovery in the laboratory because all was thinking that sometimes 100 bar is better for the machinery, space and closure.
00:00:00.381 --> 00:00:02.144
00:00:02.144 --> 00:00:04.748
00:00:04.748 --> 00:00:07.514
00:00:07.514 --> 00:00:16.195
00:00:16.195 --> 00:00:17.960
00:00:17.960 --> 00:00:23.405
00:00:23.405 --> 00:00:31.414
00:00:31.414 --> 00:00:41.340
00:00:41.340 --> 00:00:51.490
00:00:51.490 --> 00:00:52.593
00:00:52.593 --> 00:00:58.588
00:00:58.588 --> 00:01:13.250
00:01:13.250 --> 00:01:19.087
00:01:19.087 --> 00:01:21.040
00:01:21.040 --> 00:01:27.164
00:01:27.545 --> 00:01:37.212
00:01:37.212 --> 00:01:41.730
00:01:41.730 --> 00:01:45.129
00:01:45.129 --> 00:01:49.811
00:01:49.811 --> 00:01:51.665
00:01:51.665 --> 00:01:53.406
00:01:53.406 --> 00:01:56.310
00:01:56.310 --> 00:01:59.969
00:01:59.969 --> 00:02:05.448
00:02:05.448 --> 00:02:14.461
00:02:14.461 --> 00:02:36.503
00:02:36.503 --> 00:02:38.429
00:02:38.429 --> 00:02:40.881
00:02:40.881 --> 00:02:47.024
00:02:47.024 --> 00:02:50.485
00:03:06.014 --> 00:03:13.538
00:03:13.538 --> 00:03:25.207
00:03:25.207 --> 00:03:34.719
00:03:34.719 --> 00:03:38.691
00:03:38.691 --> 00:03:46.603
00:03:46.603 --> 00:03:49.628
00:03:50.211 --> 00:03:50.752
00:03:50.752 --> 00:03:54.794
00:03:54.794 --> 00:03:56.622
00:03:56.622 --> 00:03:57.667
00:03:57.667 --> 00:03:59.092
00:03:59.092 --> 00:03:59.996
00:03:59.996 --> 00:04:04.688
00:04:04.688 --> 00:04:10.651
00:04:10.651 --> 00:04:20.095
00:04:20.095 --> 00:04:23.009
00:04:23.009 --> 00:04:25.427
00:04:25.988 --> 00:04:31.411
00:04:31.411 --> 00:04:36.391
00:04:36.391 --> 00:04:46.583
00:04:46.583 --> 00:04:54.846
00:04:54.846 --> 00:05:08.747
00:05:08.747 --> 00:05:10.793
00:05:10.793 --> 00:05:16.987
00:05:16.987 --> 00:05:23.629
00:05:23.651 --> 00:05:30.430
00:05:30.800 --> 00:05:32.827
00:05:32.827 --> 00:05:34.848
00:05:34.848 --> 00:05:39.351
00:05:39.351 --> 00:05:43.271
00:05:43.271 --> 00:05:50.113
00:05:50.113 --> 00:05:58.000
00:05:58.000 --> 00:06:02.992
00:06:03.439 --> 00:06:09.745
00:06:09.745 --> 00:06:14.692
00:06:14.692 --> 00:06:19.672
00:06:19.672 --> 00:06:22.274
00:06:22.274 --> 00:06:40.648
00:06:40.648 --> 00:06:43.247
00:06:43.427 --> 00:06:44.190
00:06:44.190 --> 00:06:45.930
00:06:45.930 --> 00:06:50.661
00:06:50.661 --> 00:07:01.351
00:07:01.351 --> 00:07:06.250
00:07:07.540 --> 00:07:11.800
00:07:11.800 --> 00:07:13.646
00:07:13.646 --> 00:07:17.704
00:07:17.704 --> 00:07:22.228
00:07:22.228 --> 00:07:28.447
00:07:28.447 --> 00:07:32.069
00:07:32.069 --> 00:07:33.326
00:07:33.326 --> 00:07:35.225
00:07:35.225 --> 00:07:35.728
00:07:35.860 --> 00:07:40.295
00:07:40.295 --> 00:07:55.987
00:07:55.987 --> 00:08:02.706
00:08:02.706 --> 00:08:08.007
00:08:08.579 --> 00:08:12.879
00:08:12.879 --> 00:08:19.992
00:08:19.992 --> 00:08:23.048
00:08:23.220 --> 00:08:38.707
00:08:38.707 --> 00:08:46.227
00:08:46.227 --> 00:08:54.783
00:08:54.783 --> 00:09:09.190
00:09:10.303 --> 00:09:20.171
00:09:20.171 --> 00:09:50.778
00:09:50.778 --> 00:09:56.320
00:09:56.320 --> 00:10:07.062
00:10:07.062 --> 00:10:15.192
00:10:15.192 --> 00:10:16.195
00:10:16.275 --> 00:10:19.767
00:10:19.767 --> 00:10:30.634
00:10:30.634 --> 00:10:37.150
00:10:37.150 --> 00:10:39.154
00:10:39.154 --> 00:10:41.326
00:10:41.779 --> 00:11:08.605
00:11:08.625 --> 00:11:19.759
00:11:19.759 --> 00:11:23.649
00:11:23.649 --> 00:11:33.785
00:11:33.785 --> 00:11:39.003
00:11:39.003 --> 00:11:46.315
00:11:46.315 --> 00:11:55.972
00:11:56.340 --> 00:12:00.392
00:12:00.392 --> 00:12:18.687
00:12:19.068 --> 00:12:39.384
00:12:39.384 --> 00:12:43.863
00:12:43.863 --> 00:12:50.227
00:12:50.227 --> 00:12:53.890
00:12:53.890 --> 00:12:57.107
00:12:57.107 --> 00:12:58.311
00:12:58.311 --> 00:13:07.729
00:13:08.289 --> 00:13:12.761
00:13:12.761 --> 00:13:13.443
00:13:13.443 --> 00:13:14.908
00:13:14.908 --> 00:13:16.972
00:13:16.972 --> 00:13:32.870
00:13:32.870 --> 00:13:41.279
00:13:41.279 --> 00:13:51.506
00:13:51.506 --> 00:14:01.644
00:14:02.140 --> 00:14:03.988
00:14:04.600 --> 00:14:24.419
00:14:24.419 --> 00:14:29.072
00:14:29.072 --> 00:14:30.225
00:14:30.225 --> 00:14:34.989
00:14:35.690 --> 00:14:36.392
00:14:36.392 --> 00:14:41.451
00:14:41.451 --> 00:14:44.865
00:14:44.865 --> 00:14:48.755
00:14:48.755 --> 00:14:53.711
00:14:53.711 --> 00:14:57.590
00:14:57.590 --> 00:15:01.510
00:15:01.510 --> 00:15:09.535
00:15:09.976 --> 00:15:10.277
00:15:10.277 --> 00:15:18.933
00:15:18.933 --> 00:15:27.434
00:15:27.434 --> 00:15:46.625
00:15:47.620 --> 00:15:53.467
00:15:53.467 --> 00:15:55.947
00:15:56.148 --> 00:16:05.293
00:16:05.293 --> 00:16:16.773
00:16:16.773 --> 00:16:26.835
00:16:26.835 --> 00:16:36.169
00:16:36.169 --> 00:16:45.265
00:16:45.265 --> 00:16:52.139
00:16:52.139 --> 00:16:56.572
00:16:56.572 --> 00:17:04.730
00:17:04.730 --> 00:17:07.067
00:17:07.067 --> 00:17:11.130
00:17:11.130 --> 00:17:14.288
00:17:14.288 --> 00:17:14.650
00:17:14.650 --> 00:17:17.046
00:17:17.400 --> 00:17:27.030
00:17:27.030 --> 00:17:29.444
00:17:29.444 --> 00:17:34.685
00:17:34.685 --> 00:17:46.351
00:17:46.351 --> 00:17:57.792
00:17:57.792 --> 00:18:00.207
00:18:00.207 --> 00:18:10.166
00:18:10.166 --> 00:18:13.088
00:18:14.401 --> 00:18:21.134
00:18:21.134 --> 00:18:28.929
00:18:28.929 --> 00:18:34.153
00:18:34.153 --> 00:18:36.665
00:18:36.665 --> 00:18:45.787
00:18:45.787 --> 00:18:49.164
00:18:49.164 --> 00:18:54.555
00:18:54.555 --> 00:19:13.076
00:19:13.801 --> 00:19:15.040
00:19:15.040 --> 00:19:21.513
00:19:21.513 --> 00:19:33.500
00:19:33.500 --> 00:19:36.105
00:19:36.105 --> 00:19:41.961
00:19:41.961 --> 00:19:52.269
00:19:52.269 --> 00:20:08.847
00:20:08.847 --> 00:20:16.171
00:20:17.101 --> 00:20:18.666
00:20:18.666 --> 00:20:29.839
00:20:29.839 --> 00:20:32.609
00:20:32.609 --> 00:20:33.192
00:20:33.192 --> 00:20:34.998
00:20:34.998 --> 00:20:45.028
00:20:45.028 --> 00:20:54.632
00:20:54.632 --> 00:20:58.147
00:20:58.147 --> 00:20:59.371
00:20:59.411 --> 00:21:23.868
00:21:23.868 --> 00:21:31.167
00:21:31.167 --> 00:21:42.086
00:21:42.086 --> 00:21:47.987
00:21:47.987 --> 00:21:58.517
00:21:58.517 --> 00:22:01.650
00:22:01.859 --> 00:22:08.844
00:22:08.844 --> 00:22:17.028
00:22:17.028 --> 00:22:29.029
00:22:29.029 --> 00:22:33.846
00:22:35.484 --> 00:22:41.160
00:22:41.160 --> 00:22:47.346
00:22:47.346 --> 00:22:48.209
00:22:48.209 --> 00:22:52.667
00:22:52.667 --> 00:22:55.717
00:22:55.717 --> 00:23:04.351
00:23:04.351 --> 00:23:04.550
00:23:04.550 --> 00:23:10.885
00:23:10.885 --> 00:23:18.594
00:23:18.594 --> 00:23:21.128
00:23:21.128 --> 00:23:27.074
00:23:27.074 --> 00:23:30.630
00:23:30.630 --> 00:23:37.670
00:23:38.220 --> 00:23:38.540
00:23:38.540 --> 00:23:59.271
00:23:59.271 --> 00:24:02.131
00:24:02.131 --> 00:24:11.587
00:24:11.587 --> 00:24:17.664
00:24:17.664 --> 00:24:29.374
00:24:30.119 --> 00:24:35.353
00:24:35.353 --> 00:24:42.371
00:24:42.371 --> 00:24:45.369
00:24:45.369 --> 00:24:51.165
00:24:51.165 --> 00:24:59.029
00:24:59.029 --> 00:25:07.692
00:25:07.692 --> 00:25:24.232
00:25:24.574 --> 00:25:28.690
00:25:28.690 --> 00:25:30.788
00:25:31.279 --> 00:25:31.480
00:25:31.480 --> 00:25:36.972
00:25:36.972 --> 00:25:48.728
00:25:48.728 --> 00:26:07.181
00:26:07.181 --> 00:26:11.590
00:26:11.590 --> 00:26:16.307
00:26:17.269 --> 00:26:26.943